ICST · Fans category
ICST logo International Cooling Solutions (Thailand)
MenuClose

Cooling tower gearbox in Thailand

A cooling tower gearbox is the right angle speed reducer between the motor and the fan. It lowers the motor speed to the fan speed and multiplies torque, so the fan blades turn at the rotational speed the tower is designed for. Inside, bevel gears turn the drive through 90 degrees. Because it runs continuously in high humidity and high temperatures, a failed gear box stops the fan and takes the tower down, with no heat rejection and unplanned downtime for the process. International Cooling Solutions (Thailand), known as ICST, supplies replacement cooling tower gearboxes and parts for induced draft towers in power plants and large factories in Thailand, including Amarillo, Sumitomo and Hansen gearboxes.

Request a gearbox quote Call +66 2 661 7723

Cooling tower gearbox and output shaft

This page is for plant engineers and maintenance teams who need a replacement or repair for a cooling tower fan drive. It shows the gear box options we supply, single or double reduction, how to choose, and what to send for a quote.

Cooling tower gearboxes we supply

Models, sizes and specifications
  • Amarillo single reduction gearbox for industrial cooling tower fan drives: right angle gear drives, single reduction.

  • Amarillo double reduction gearbox: right angle gear drives, double reduction, with design features and ratings in the manufacturer catalog.

  • Sumitomo Paramax SFC-055 cooling tower gearbox: a cooling tower drive gearbox sized for mid range fan loads.

  • Sumitomo Hansen P4 gearbox: a single stage gearbox for cooling tower fan drives, built for compact reduction needs.

  • Other major brands, all sizes and ratios. Special order gears and parts are welcome.

  • Replacement or repair confirmed against your drive: send the gearbox model or the nameplate details and our team confirms the replacement or the repair.

For one model series in detail, see our Amarillo A Series gearbox page.

Single or double reduction gearbox?

  • Single reduction: one gear mesh between the input and output. It is the simpler arrangement and is common where the motor speed and fan speed need a moderate reduction.

  • Double reduction: two gear meshes. It is used where a larger overall ratio is needed, for lower fan speeds from a higher-speed motor.

  • The choice follows the motor speed, the fan speed and the ratio of the unit you replace. Match the existing gearbox model and nameplate, and ask us if you are changing the fan speed.

How to choose a cooling tower gearbox

  • Motor power and motor speed, and fan speed, which together set the ratio.

  • Gearbox manufacturer, model, ratio, and shaft arrangement of the existing unit.

  • The distance between shaft ends, which depends on the drive shaft.

  • Thermal rating and operating conditions: high operating temperatures, high humidity and moisture.

  • Starts per day, speed type, whether a variable frequency drive (VFD) is used, and reversing.

  • Fan details: diameter, number of fan blades and any planned change of fan speed.

  • Your maintenance plan: oil seals, lubrication system, oil change practice and inspection intervals.

Common gearbox failures and root causes

Most gearbox failures have a root cause that should be removed when the unit is replaced:

  • Lubrication: low oil, contaminated oil or failed oil seals that let moisture in.

  • Vibration: fan imbalance, shaft misalignment or a worn drive shaft, which damage bearings and gears.

  • Operation: frequent starts, VFD-related resonance or running outside the rated duty.

  • Wear: worn bearings, gear wear and friction that show up as noise or metal in the oil.

Replacing a gearbox is a good time to check the fan, motor and drive shaft together, since they are the mechanical components of the same drive.

What to send for a cooling tower gearbox quote

Complete our Gear Box Inquiry Form and add it to your request. It asks for:

  • owner, location, bid and delivery dates, and the number of gearboxes required;

  • the distance between shaft ends;

  • motor details: power, speed, shaft diameter, keyway, frame size, starts per day, speed type, VFD and reversing.

Photos and the gearbox nameplate help our parts team confirm the fit.

Gear Box Inquiry Form (PDF)

Cooling tower gearbox questions

What does a cooling tower gearbox do?

It reduces motor speed to fan speed and transmits torque to the fan through a right angle drive.

What causes cooling tower gearbox failure?

Typically lubrication problems, vibration and misalignment, frequent starts or moisture in the oil. A check of the drive during replacement helps stop the failure from repeating.

Can I replace a gearbox with a different make or model?

Sometimes, if the ratio, shaft arrangement, mounting and rating match. Send the nameplate or model and our team confirms whether the replacement fits.

How do I choose between single and double reduction?

By the total ratio you need and the unit you are replacing. Send the nameplate and we confirm.

Do you supply gears and parts, or only complete gearboxes?

We supply complete gearboxes, and special order gears and parts are welcome.

How much does a cooling tower gearbox cost?

Cost depends on brand, size and ratio. We quote after checking your details.

Need a replacement cooling tower gearbox?

Send the Gear Box Inquiry Form, the nameplate and photos, and our parts team will confirm the gearbox and quote. Request a gearbox quote or call our Bangkok team on +66 2 661 7723.

Request a quote

ICST

This website does not set any cookies itself. Our security provider, Cloudflare, sets the cookies listed below to protect the site, and the site keeps two items of browser storage in your current tab. We list the browser storage here too, although it is not a cookie.

Language links

If you use a language link, the page opens on Google Translate (translate.goog). Google may set its own cookies on its own domain, under Google’s terms. We do not control them.

Your choices

Close the browser tab to clear the stored items. Choose “Start over” in the quote form to clear an unsent request. You can also block or delete cookies and site data in your browser settings. Blocking the security cookies may stop the quote form or other pages from working.

Analytics and advertising

We do not use analytics tools or advertising cookies. We will update this notice before we start.

Service providers and effective date

Z.com hosting in Thailand, which hosts the website and the system where requests are stored.

Cloudflare, which provides content delivery and security protection and sets the cookies listed above.

Effective date: 13 November 2026. Questions: use the form on our contact page.